I'm using Simscape features in Simulink. In the "Three-Phase Source" block the setting of the "Phase to phase voltage" parameter is defined as RMS. But I can not get the nominal values. I can only apply a division by root of 2. Is it right or am I making a mistake?
0 件のコメント
回答 (1 件)
Joel Van Sickel
2020 年 9 月 2 日
Hello Ademir,
the RMS voltage is Vpeak/sqrt(2). Vline to line = Vphase*sqrt(3). It sounds like you are doing it correctly.
Regards,
Joel
2 件のコメント
Maya
2023 年 10 月 5 日
I am using the Simscape 3 pahse source ( specialized Power systems) to power a 3 phase induction motor. However, I observe that the phase to phase voltages between the three phases are showing slightly different values. None of the values match the setting of the model namely 400V rms. The .slx file is attached. ![](https://www.mathworks.com/matlabcentral/answers/uploaded_files/1502394/image.jpeg)
![](https://www.mathworks.com/matlabcentral/answers/uploaded_files/1502394/image.jpeg)
Joel Van Sickel
2023 年 10 月 9 日
Hello Maya,
you have your source set to 50 hz but the RMS blocks set to 60 hz. They need to the be same for the calculation to work.
Regards,
Joel