Load flow convergence problem
9 ビュー (過去 30 日間)
古いコメントを表示
Hello,
I have a problem with the attached Simulink Scheme. The generator has been put as a Swing bus, while the load as a PQ bus I have tried to run a load flow simulation on the scheme, but it seems I have no convergence.
What I have noticed is that: -By removing the PI section line, while maintaining all the rest, the load flow actually converges to a solution. Of course, same goes if remove both PI section line and the transformer. -By reducing the load (up to 14MW and up to 14Mvar) the system still converges, even if I keep the PI section line. -By replacing the load (a R-L parallel load) with an R-L series load (of equal P and Q) the system still converges.
Could you please help me figuring out what the problem is? Thanks in advance, Davide
2 件のコメント
Franklin Ngo
2019 年 5 月 19 日
Hello,
I checked your system. Your problem is about transient stability. The maximum power: Pmax = E'*Eb/X ( for more details, please read the chapter 13. transient stability. - 13.1 an elementary view of transient stability - book: [prabha kundur] power system stability and control). Your power is too large, then your impedance have to be reduced. Please check the attached file.
Kamilu Sanusi
2023 年 3 月 9 日
@Franklin Ngoplease I am similar problem, on IEEE 9 bus system, if i set my load as constant impedance load, the active power injected at the generator bus becomes greater than the specified mechnical power input. The active and reactive power PL & QL of the load also rises.
Please what is the likely problem, all other loads are okay
Thank you
回答 (1 件)
Willim
2018 年 11 月 29 日
Thank you for sharing the problem. I would like to contact you if you would like to help each other in this problem.