DAQ with ENET-9163 and NI 9237 National Instruments
    11 ビュー (過去 30 日間)
  
       古いコメントを表示
    
Hello,
I can't open a channel of the NI 9237 Device in Matlab using R2011a is it a device support problem or is there any solution? That's the device info i'm getting:
>> get(deviceInfo)
     IsSimulated: false
          Vendor: National Instruments
              ID: 'ENET-14E1636'
           Model: 'ENET-9237'
      Subsystems: empty
     Description: 'National Instruments ENET-9237'
RecognizedDevice: false
and when i want to open a analoginput:
   s.addAnalogInputChannel('ENET-14E1636', 'ai0', 'Voltage');
  ??? The requested subsystem 'AnalogInput' does not exist on this device.
Thanks for any help!
0 件のコメント
回答 (2 件)
  Manisha
    
 2012 年 2 月 21 日
        Hi Dirk,
Support for NI 9237 was added in R2011b. NI 9237 supports only bridge measurements, so if you use R2011b , you should be able to use this device as
s = daq.createSession('ni');
s.addAnalogInputChannel('Dev5', 0, 'Bridge');
Hope that helps,
Manisha
0 件のコメント
  Vinh Dang
 2015 年 3 月 5 日
        
      編集済み: Vinh Dang
 2015 年 3 月 5 日
  
      Hello, In my application, I have a cDAQ configuration with AI modules 9234 (for accelerometers), 9237 (for pressure and load cell) and 9215 (for proximity and temperature). All modules are put in one chassis cDAQs-9178. What is the valid sampling rate for this?
Thanks for your help!
0 件のコメント
参考
カテゴリ
				Help Center および File Exchange で Data Acquisition Toolbox Supported Hardware についてさらに検索
			
	Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!