IEEE 14 bus Power flow code
46 ビュー (過去 30 日間)
古いコメントを表示
Hi Anybody can send me the IEEE 14 bus power flow program.
Yunus
1 件のコメント
kalana agampodi
2021 年 10 月 6 日
Chech the link. I complited it and also did fast decoupled power flow, Q limits cotrol by using Newton Raphson and using Crout's method.
回答 (3 件)
Muruganandham Subramanian
2011 年 12 月 13 日
function [baseMVA, bus, gen, branch, areas, gencost] = case14
%%system MVA base
baseMVA = 100;
%%bus data
% bus_i type Pd Qd Gs Bs area Vm Va baseKV zone Vmax Vmin
bus = [
1 3 0 0 0 0 1 1.06 0 0 1 1.06 0.94;
2 2 21.7 12.7 0 0 1 1.045 -4.98 0 1 1.06 0.94;
3 2 94.2 19 0 0 1 1.01 -12.72 0 1 1.06 0.94;
4 1 47.8 -3.9 0 0 1 1.019 -10.33 0 1 1.06 0.94;
5 1 7.6 1.6 0 0 1 1.02 -8.78 0 1 1.06 0.94;
6 2 11.2 7.5 0 0 1 1.07 -14.22 0 1 1.06 0.94;
7 1 0 0 0 0 1 1.062 -13.37 0 1 1.06 0.94;
8 2 0 0 0 0 1 1.09 -13.36 0 1 1.06 0.94;
9 1 29.5 16.6 0 19 1 1.056 -14.94 0 1 1.06 0.94;
10 1 9 5.8 0 0 1 1.051 -15.1 0 1 1.06 0.94;
11 1 3.5 1.8 0 0 1 1.057 -14.79 0 1 1.06 0.94;
12 1 6.1 1.6 0 0 1 1.055 -15.07 0 1 1.06 0.94;
13 1 13.5 5.8 0 0 1 1.05 -15.16 0 1 1.06 0.94;
14 1 14.9 5 0 0 1 1.036 -16.04 0 1 1.06 0.94;
];
save baseMVA baseMVA;
save bus bus;
%%generator data
% bus Pg Qg Qmax Qmin Vg mBase status Pmax Pmin
gen = [
1 232.4 -16.9 10 0 1.06 100 1 332.4 0;
2 40 42.4 50 -40 1.045 100 1 140 0;
3 0 23.4 40 0 1.01 100 1 100 0;
6 0 12.2 24 -6 1.07 100 1 100 0;
8 0 17.4 24 -6 1.09 100 1 100 0;
];
save gen gen;
%%branch data
% fbus tbus r x b rateA rateB rateC ratio angle status
branch = [
1 2 0.01938 0.05917 0.0528 9900 0 0 0 0 1;
1 5 0.05403 0.22304 0.0492 9900 0 0 0 0 1;
2 3 0.04699 0.19797 0.0438 9900 0 0 0 0 1;
2 4 0.05811 0.17632 0.034 9900 0 0 0 0 1;
2 5 0.05695 0.17388 0.0346 9900 0 0 0 0 1;
3 4 0.06701 0.17103 0.0128 9900 0 0 0 0 1;
4 5 0.01335 0.04211 0 9900 0 0 0 0 1;
4 7 0 0.20912 0 9900 0 0 0.978 0 1;
4 9 0 0.55618 0 9900 0 0 0.969 0 1;
5 6 0 0.25202 0 9900 0 0 0.932 0 1;
6 11 0.09498 0.1989 0 9900 0 0 0 0 1;
6 12 0.12291 0.25581 0 9900 0 0 0 0 1;
6 13 0.06615 0.13027 0 9900 0 0 0 0 1;
7 8 0 0.17615 0 9900 0 0 0 0 1;
7 9 0 0.11001 0 9900 0 0 0 0 1;
9 10 0.03181 0.0845 0 9900 0 0 0 0 1;
9 14 0.12711 0.27038 0 9900 0 0 0 0 1;
10 11 0.08205 0.19207 0 9900 0 0 0 0 1;
12 13 0.22092 0.19988 0 9900 0 0 0 0 1;
13 14 0.17093 0.34802 0 9900 0 0 0 0 1;
];
save branch branch;
%%----- OPF Data -----%%
%%area data
areas = [
1 1;
];
%%generator cost data
% 1 startup shutdown n x1 y1 ... xn yn
% 2 startup shutdown n c(n-1) ... c0
gencost = [
2 0 0 3 0.0430293 20 0;
2 0 0 3 0.25 20 0;
2 0 0 3 0.01 40 0;
2 0 0 3 0.01 40 0;
2 0 0 3 0.01 40 0;
];
return;
this is the data file. you just try it for powerflow solution...
8 件のコメント
kalana agampodi
2021 年 10 月 18 日
https://www.mathworks.com/matlabcentral/answers/23781-ieee-14-bus-power-flow-code#comment_1771566
POORNIMA JAYAPRAKASH
2014 年 1 月 22 日
Thanks for Data file I need also Power flow solution code. Please help me .....
0 件のコメント
sonu kumar
2021 年 7 月 31 日
any one can send me matlab code for optimal pmu placement by using integer linear programming for line outage and normal condition case. please help me. please send code on gmail enggsonubairwa@gmail.com
3 件のコメント
kalana agampodi
2021 年 10 月 6 日
編集済み: Walter Roberson
2021 年 10 月 7 日
kalana agampodi
2021 年 10 月 6 日
Check out the link I send I completed it.
I used Newton Raphson to get it to converge and also used fast decoupled power flow analysis and Q limit control.
Let me know if you have questions.
Good luck!!
参考
カテゴリ
Help Center および File Exchange で Power and Energy Systems についてさらに検索
Community Treasure Hunt
Find the treasures in MATLAB Central and discover how the community can help you!
Start Hunting!