メインコンテンツ

hisl_0041: Configuration Parameters > Solver > Solver options

R2026b

Configure fixed-step discrete solver for production code generation

Usage: High-Integrity System Modeling

Guideline ID: hisl_0041

Rules

For models used to develop high-integrity systems, in the Configuration Parameters dialog box, on the Solver pane, set parameters for solvers as follows:

hisl_0041: Configuration Parameters > Solver > Solver options
A

Type to Fixed-step.

Rationale

Generate code that is valid for production code generation.

Verification

Check safety-related solver settings for solver options (Simulink Check)

B

Solver to discrete (no continuous states).

Rationale

Generate code that is valid for production code generation.

Verification

Check safety-related solver settings for solver options (Simulink Check)

Tips

  • Generating code for production requires a fixed-step, discrete solver.

Industry Standards

  • DO-331 Section MB.6.3.1.g—Algorithms are accurate

    DO-331 Section MB.6.3.2.g—Algorithms are accurate

  • IEC 61508-3, Table A.3 (3) 'Language subset'

  • IEC 62304, 5.5.3 - Software Unit acceptance criteria

  • ISO 26262-6, Table 1 (1b) 'Use of language subsets'

  • EN 50128, Table A.4 (11) 'Language Subset'

  • EN 50657, Table A.4 (11) 'Language Subset'

Version History

Introduced in R2010a

expand all

See Also