Plate Condenser Evaporator (TL-2P)
Plate geometry condenser evaporator between two-phase fluid and thermal liquid networks
Since R2024a
Libraries:
Simscape /
Fluids /
Heat Exchangers /
Two-Phase Fluid - Thermal Liquid
Description
The Plate Condenser Evaporator (TL-2P) block models a plate heat exchanger between a thermal liquid and a two-phase fluid network. The block models the heat transfer between the thermal liquid and the two-phase fluid based on the effectiveness-NTU method. Heat transfer can occur in either direction between the two fluids.
The block uses the Effectiveness-NTU (E-NTU) method to model heat transfer through the shared plate walls. You can also account for heat transfer through the plate itself by selecting the Plate thermal resistance parameter. The block models fouling on the exchanger walls, which increases thermal resistance and reduces the heat exchange between the two fluids.
The two-phase fluid flows use a boundary-following model to track the subcooled liquid, vapor-liquid mixture, and superheated vapor in three zones. The relative amount of space a zone occupies in the system is called a zone fraction.
Plate Heat Exchanger Geometry
Plate heat exchangers consist of a series of clamped-together plates. Each plate has portholes for the fluid to flow through and gaskets around the portholes and the plate sides to contain the liquid. The gasket pattern alternates between the plates so that on each side of the plate, one fluid flows across the plate while the other fluid flows through it. This design results in alternating layers of hot and cold fluid. This figure shows a section of counter-flow in a plate heat exchanger.
This figure shows an individual plate and a cross-section of two adjacent plates. In the individual plate image, the thick lines represent the gaskets and the dotted lines represent the plate corrugation. The block assumes that the flow channel gap between the plates equals the corrugation depth, b.
On this plate, one fluid flows from the top-right port hole across the plate to the bottom-right port hole. The other fluid flows through the gasket on the two left-side portholes and not touch the plate on this side. The plate corrugation patterns increase structural stiffness, surface area, and turbulence.
Because fluid flows along both sides of each plate, the total fluid volume is
where:
Np is the value of the Number of plates parameter.
Lp is the value of the Plate length parameter.
Wp is the value of the Plate width parameter.
b is the value of the Spacing between plates parameter.
The volume of each fluid is half of the total volume. The flow cross-sectional area, S, for each fluid is
The total projected surface area of the plates, assuming no corrugation, is
Each fluid has half of the total heat transfer surface area
where the area enlargement factor, ϕ, accounts for the increased surface area due to the corrugation
The hydraulic diameter for each fluid is
Effectiveness-NTU Heat Transfer
The block calculates the heat transfer rate in three parts to correspond with the with the three fluid zones that occur on the two-phase fluid side of the heat exchanger.
The convective heat transfer in a zone is
where:
CMin is the lesser of the heat capacity rates of the two fluids in that zone. The heat capacity rate is the product of the fluid specific heat, cp, and the fluid mass flow rate. CMin is always positive.
TIn,2P is the zone inlet temperature of the two-phase fluid.
TIn,TL is the zone inlet temperature of the thermal liquid.
ε is the heat exchanger effectiveness.
Effectiveness is a function of the heat capacity rate and the number of transfer units, NTU, and varies based on the heat exchanger flow arrangement. NTU is
where:
z is the individual zone fraction.
R is the total thermal resistance between the two flows due to convection, conduction, and any fouling on the plates:
where:
U is the convective heat transfer coefficient of the respective fluid.
F is the value of the Fouling factor parameter on the two-phase fluid or thermal liquid side.
RW is the thermal resistance through the plates. If you select Plate thermal resistance, where t is the value of the Plate thickness parameter and kp is the value of the Plate thermal conductivity parameter.
If you clear the Plate thermal resistance check box, RW = 0.
The total convective heat transfer rate between the fluids is the sum of the heat transferred in the three zones by the subcooled liquid, QL, liquid-vapor mixture, QM, and superheated vapor, QV,
The heat exchanger effectiveness varies according to the flow configuration and fluid stage. The effectiveness is for all flow arrangements in the liquid-vapor mixture zone.
For the subcooled liquid and the superheated vapor zones, when Flow
arrangement is Parallel flow
For the subcooled liquid and the superheated vapor zones, when Flow
arrangement is Counter flow
CR is the ratio between the heat capacity rates of the two fluids
Conductive Heat Transfer
The conductive heat transfer in a zone is
where:
Tout,2P is the zone outlet temperature of the two-phase fluid.
Tout,TL is the zone outlet temperature of the thermal liquid.
Rcond is the total conductive thermal resistance between the two flows,
where:
AW is the wall surface area.
k is the thermal conductivity of each fluid.
DH is the hydraulic diameter.
The total heat transfer is the sum of the convective and conductive heat transfer. The conductive heat transfer is negligible compared to the convective heat transfer. When the flow rate is zero, the convective heat transfer is also zero. However, because heat transfer from convection and conduction operate independently of each other, there is still conductive heat transfer even when the convective heat transfer is zero.
Pressure Loss
For both fluids and pressure loss parameterizations, the pressure loss between each port and the internal node is
where:
ṁA is the mass flow rate through port A1 or A2 when the block calculates the values for the thermal liquid and two-phase networks, respectively.
ṁB is the mass flow rate through port A1 or A2 when the block calculates the values for the thermal liquid and two-phase networks, respectively.
ρ is the fluid density.
ξports is the value of the Loss coefficient for inlet and outlet manifolds and ports parameter.
Sport,A is the value of the Cross-sectional area at port A1 or Cross-sectional area at port A2 parameter, when the block calculates the values for the thermal liquid and two-phase networks, respectively.
Sport,B is the value of the Cross-sectional area at port B1 or Cross-sectional area at port B2 parameter, when the block calculates the values for the thermal liquid and two-phase networks, respectively.
When the Pressure loss model parameter is
Friction factor
, you use the Darcy friction
factor for flow between corrugated plates parameter to specify a
single constant friction factor for the fluid.
fDarcy is the value of the
Darcy friction factor for flow between corrugated plates
parameter.
When the Pressure loss model parameter is
Correlation for flow between corrugated plates
, the
block calculates the Darcy friction factor based on the plate geometry data and
Reynolds number from [3].
The Reynolds number is where μ is the dynamic viscosity. When the Reynolds number is between 200 and 1000,
When the Reynolds number is greater than 2000,
The block uses a smooth cubic transition between these regions and for Reynolds numbers between 1000 and 2000. For Reynolds numbers below 200, the block calculates fDarcy from a laminar friction constant that ensures numerical robustness as the flow goes to 0.
Heat Transfer Coefficient
The heat transfer coefficient, U, is
The heat transfer calculations depend on the value of the Heat transfer coefficient model parameter and the two-phase fluid zone. When the thermal liquid and two-phase fluid are in the subcooled liquid or superheated vapor zone, k is the fluid thermal conductivity. When the two-phase fluid is in the saturated liquid-vapor mixture zone, k is the saturated liquid thermal conductivity.
When Heat transfer coefficient model is
Colburn equation
, the block calculates the heat
transfer coefficient from data by using the Colburn correlation
coefficients.
When the thermal liquid and two-phase fluid are in the subcooled liquid or superheated vapor zone, the Nusselt number is
where a, b, and c are the first, second, and third elements in the Coefficients [a, b, c] for a*Re^b*Pr^c parameter and Pr is the Prandtl number.
When the two-phase fluid is in the saturated liquid-vapor mixture zone, the Nusselt number from [2] is
where:
ReSL and PrSL are the Reynolds number and the Prandtl number of the saturated liquid, respectively.
vSL and vSV are the saturated liquid and vapor specific volumes, respectively.
xin is the vapor quality at the start of the saturated liquid-vapor mixture zone.
xout is the vapor quality at the end of the saturated liquid-vapor mixture zone.
When Heat transfer coefficient model is
Correlation for flow between corrugated plates
,
the block calculates the heat transfer coefficient based on the plate geometry
data.
When the thermal liquid and two-phase fluid are in the subcooled liquid or superheated vapor zone, the Nusselt number from [3] is
where:
c1, c2, and c3 are the first, second, and third elements in the Coefficients for Martin correlation parameter.
Pr is the Prandtl number.
When the two-phase fluid is in the saturated liquid-vapor mixture zone, the Nusselt number from [2] is
Conservation Equations
The total mass accumulation rate in the two-phase fluid is
where:
M2P is the total mass of the two-phase fluid.
A2 is the mass flow rate of the fluid at port A2.
B2 is the mass flow rate of the fluid at port B2.
The block relates the change in specific internal energy to the heat transfer by the fluid by using the equation
where:
u2P is the two-phase fluid specific internal energy.
φA1 is the energy flow rate at port A1.
φB1 is the energy flow rate at port B1.
Q is heat transfer rate.
The total mass accumulation rate in the thermal liquid is
The energy conservation equation is
where:
ϕA1 is the energy flow rate at port A1.
ϕB1 is the energy flow rate at port B1.
The heat transferred to or from the thermal liquid, Q, equals the heat transferred from or to the two-phase fluid.
Ports
Output
Conserving
Parameters
References
[1] Shah, Ramesh K., and Dusan P. Sekulic. Fundamentals of heat exchanger design. John Wiley & Sons, 2003.
[2] Longo, Giovanni A., Giulia Righetti, and Claudio Zilio. "A new computational procedure for refrigerant condensation inside herringbone-type Brazed Plate Heat Exchangers." International Journal of Heat and Mass Transfer 82 (2015): 530-536.
[3] Martin, Holger. "A theoretical approach to predict the performance of chevron-type plate heat exchangers." Chemical Engineering and Processing: Process Intensification 35.4 (1996): 301-310.
Extended Capabilities
Version History
Introduced in R2024a